FeatureDescription
Maximum number of input data per assembly instance

504 bytes

Maximum number of output data per assembly instance504 bytes
Maximum number of assemblies10
IO Connection Types (implicit)

Exclusive Owner, Listen Only,

Input only
IO Connection Trigger Types

Cyclic, minimum 1 ms*
Application Triggered, minimum 1 ms*
Change Of State, minimum 1 ms*

Explicit MessagesConnected and unconnected
Unconnected Message Manager (UCMM)supported
Max. number of connections

Class 1: 5

Class 3: 10

UCMM: 10

Max. number of user specific objects20
Predefined standard objects

Identity Object (0x01)
Message Router Object (0x02)
Assembly Object (0x04)
Connection Manager (0x06)
DLR Object (0x47)
QoS Object (0x48)
TCP/IP Interface Object (0xF5)
Ethernet Link Object (0xF6)
LLDP Management Object (0x109)

DHCPsupported
BOOTPsupported
Baud rates10 and 100 MBit/s
Duplex modesHalf Duplex, Full Duplex, Auto-Negotiation
MDI modesMDI, MDI-X, Auto-MDIX
Data transport layerEthernet II, IEEE 802.3
Address Conflict Detection (ACD)supported
DLR (ring topology)supported
Integrated switchsupported
CIP Reset servicesIdentity Object Reset Service of Type 0 and 1

Configuration

Configuration is done by sending packets to the stack or by using SYCON.net configuration database.