Background

...

Some EtherCAT specific features can´t be configured using SyCon.net

...

. Even tho they are supported by our firmware. Those features are, for exampleOversampling, Hot-Connect, EoE (Ethernet over EtherCAT)

...

or FoE (Fileaccess over EtherCAT).

...

Our cifx

...

cards can, in case of EtherCAT, not only be configured using a configuration database (config.nxd)

...

from SyCon.net

...

or an applicative configuration. Instead it can also work with an ENI (EtherCAT Network Information)

...

Vorgehen

  • Öffnen sie den TwinCAT System Manager und starten ein neues Projekt.
  • Fügen sie nun zuerst einen generischen EtherCAT Master hinzu:

Image Removed

  • Konfigurieren sie das gesamten EtherCAT Netzwerk mit allen Slaves und den entsprechenden Einstellung, welche in SyCon.net fehlten.
    • Ein Rechtsklick auf den Slave, lässt sie diesen z.B. zu einer Hot-Connect Gruppe hinzufügen. In den "Erweiterten Einstellungen" vom Master und den Slaves finden sich z.B. Möglichkeiten EoE zu konfigurieren.

Image Removed

  • Ist das Netzwerk soweit eingerichtet markieren sie den Master und klicken auf "Export Konfigurationsdatei...".
  • Die exportierte Datei benennen sie bitte "ethercat.xml". Denn nur wenn die Datei genau diesen Namen hat, erkennt unsere Firmware sie als gültige Konfigurationsdatei an.

Image Removed

...

file, that is conform to the  EtherCAT specification. One of the most important tools in this regards is TwinCAT from Beckhoff GmbH. The following screenshots are taken from the German version of TwinCAT 2. Below it´s shown, how to export the ENI and how to download it to the cifx card. Using TwinCAT 3 is the same, just some names and colors are changed.

Procedure 

  • Open the TwinCAT System Manager and start a new Project

EtherCAT Master configuration

  • First add a generic EtherCAT Master:

Image Added

  • Configure the entire EtherCAT network with all slaves and there needed settings, which might be missing in SyCon.net.

Additional Configurations (Hot-Connect, EOE ....)

  • With a right click on the slave you can f.e. add him to a hot-connect group. In "Advanced Settings..." from master or slave (Highlight the device → click on the Tab "EtherCAT" → "Advanced Settings...") you can find settings for EoE for example.

Image Added

Export Configuration File

  • After the network is configured highlight the master and click "Export Configuration File...".
  • You have to name the exported file "ethercat.xml". Because just with this exact name our firmware will accept the ENI file as it´s new configuration file.

Image Added

Load Configuration File ethercat.xml

  • To load the ENI file into our cifx card you need the "cifx Setup" tool, it will be installed together with the installation of the cifx driver.
  • The tool is located in the following folder (Windows 10): "C:\Program Files\cifX Device Driver" oder in den Systemsteuerungen.
  • Wählen sie nun den Kommunikationskanal
  • . It can also be reached from the system control.

  • Choose the communication channel (CH#0) der of your cifx Karte aus, welche als Master fungieren soll und laden die ENI über die Schaltfläche "Add" in den Treiber.
    • Wichtig: Sollte sich noch eine andere Konfiguration im Treiber befinden wird diese bevorzugt genutzt. Es ist also erforderlich diese über die Schaltfläche "Remove" zu entfernen.

Image Removed

    Nach einem Neustart der cifx läuft diese nun mit der ENI Datei als Konfiguration
  • card, that is the EtherCAT master and load the ENI configuration file to the driver, using the "Add" button.

Image Added

Note

Should there be another configuration file (config.nxd) present in the driver, it will be prioritised. It is therefor necessary to remove it via the "Remove" button, first.

  • After a restart of the cifx it will run with the ENI as it´s configuration.