Error Description


If external Hilscher devices via USB or TCP / IP are no longer available, a possible cause may be a faulty operation of the so-called ODMV3 service.

This happens when the connection to the device is "violently" interrupted during a running software session, for example with Sycon.NET. The ODMV3 service loses the access point and can not recover it.

It is therefore essential to avoid disconnecting the USB or network connection during a running software session.



ODMV3 in System Tray

The ODMV3 service is located in the system tray of Windows and is represented by a green PC card.

When the mouse pointer is moved over the icon, the current number of active connections is displayed.



ODMV3-Control (Restart)

By right-clicking and choosing "Service", you reach the control options.

Here the ODMV3 service can be stopped and restarted.


If the ODMV3 icon is not visible in the system tray, the service can be controlled manually through Windows Services Management.

Click on Start and search for "Services". There you search for the ODMV3 and stop / start the service via the provided buttons.