Features - V1
Key Features
- Cyclic data Exchange (1..16 occupied stations)
- SLMP
Supported Protocols
- SLMP Server
- SLMP Client
On this page
Technical Data
Feature | Description |
---|---|
Maximum number of cyclic RY data Maximum number of cyclic RX data Maximum number of cyclic RWw data Maximum number of cyclic RWr data | 128 bytes (1024 bits) 128 bytes (1024 bits) 512 words (16 bit) 512 words (16 bit) |
Occupied stations | 1 ā¦ 16 (1 station has 64 bits RY data, 32 words RWw data, 64 bits RX data, and 32 words RWr data) |
Acyclic communication | SLMP Server and Client |
UDP ports | Cyclic data 61450 (UDP) Discovery and SLMP Server 61451 (UDP) SLMP Parameter 45237 (UDP) SLMP Communication 20000 (UDP) |
Data transport layer | Ethernet II, IEEE 802.3, 100 MBit/s |
Configuration
Configuration is done by sending packets to the stack or by using SYCON.net configuration database.
Diagnostic
Some elementary diagnosis information can be read using the service āGet Status Serviceā.