Features - V1

Key Features

  • Cyclic data Exchange (1..16 occupied stations)
  • SLMP

Supported Protocols

  • SLMP Server
  • SLMP Client
On this page


Technical Data

FeatureDescription

Maximum number of cyclic RY data

Maximum number of cyclic RX data

Maximum number of cyclic RWw data

Maximum number of cyclic RWr data

128 bytes (1024 bits)

128 bytes (1024 bits)

512 words (16 bit)

512 words (16 bit)

Occupied stations

1 ā€¦ 16

(1 station has 64 bits RY data, 32 words RWw data,

64 bits RX data, and 32 words RWr data)

Acyclic communicationSLMP Server and Client

UDP ports

Cyclic data 61450 (UDP)

Discovery and SLMP Server 61451 (UDP)

SLMP Parameter 45237 (UDP)

SLMP Communication 20000 (UDP)

Data transport layerEthernet II, IEEE 802.3, 100 MBit/s

Configuration

Configuration is done by sending packets to the stack or by using SYCON.net configuration database.

Diagnostic

Some elementary diagnosis information can be read using the service ā€œGet Status Serviceā€.