Key Features
- Implicit Messaging: class 0 or class 1
- Explicit Messaging Unconnected / Connected (class 3)
- Connection Application Types: Exclusive Owner, Input Only, Listen Only
- Device Level Ring (DLR) - Media Redundancy
- Address Conflict Detection (ACD)
- Quality of Service (QoS)
- Object model can be extended by implementing own CIP objects (necessary to support CIP profiles)
- CIP Sync
- QuickConnect (Fast Startup)
- NULL-ForwardOpen
- "Ready" for CIP Safety (provides all necessary features and interfaces to attach a CIP Safety stack on top)
Supported Protocols
- TCP/IP, UDP/IP
- DLR
- DHCP / BOOTP
- IEEE 802.3
- IEEE 802.1Q
- LLDP
- SNMP
Technical Data
Feature | Description |
---|---|
Maximum number of input data per assembly instance | 504 bytes |
Maximum number of output data per assembly instance | 504 bytes |
Maximum number of assemblies | 10 |
IO Connection Types (implicit) | Exclusive Owner, Listen Only, Input only |
IO Connection Trigger Types | Cyclic, minimum 1 ms* |
Explicit Messages | Connected and unconnected |
Unconnected Message Manager (UCMM) | supported |
Max. number of connections | Class 1: 5 Class 3: 10 UCMM: 10 |
Max. number of user specific objects | 20 |
Predefined standard objects | Identity Object (0x01) |
DHCP | supported |
BOOTP | supported |
Baud rates | 10 and 100 MBit/s |
Duplex modes | Half Duplex, Full Duplex, Auto-Negotiation |
MDI modes | MDI, MDI-X, Auto-MDIX |
Data transport layer | Ethernet II, IEEE 802.3 |
Address Conflict Detection (ACD) | supported |
DLR (ring topology) | supported |
Integrated switch | supported |
CIP Reset services | Identity Object Reset Service of Type 0 and 1 |
On this page