Key Features
- Number of supported slaves: max. 62 slaves
- Support of 6 combined transaction types (CTT) available (CTT1 to CTT5 and CTT for Safety at work)
- AS-Interface specification 3.0 Revision 2
Supported Protocols
- Support of slave profiles
16 bit input or output S-7.3
Complex field devices S-7.4
Combi field devices S-7.5.5
Combi field devices S-7.A.5
Serial communication field devices S-B.A.5
4 inputs/4 outputs in extended addressing mode S-7.A.7
8 inputs/8 outputs in extended addressing mode S-7.A.A
16 inputs in extended addressing mode S-7.A.
Dual 16 inputs in extended addressing mode S-7.A.
High speed 16 bit inputs and outputs S-6.
Safety at Work Safety at Work input slaves S-0.
Safety at Work Safety at Work input slaves with standard outputs S-7.
Technical Data
The data below applies to AS-Interface Master firmware and stack version 2.3.x
Feature | Description |
---|---|
Maximum number of supported slaves | Max. 62 slaves |
Maximum number of total cyclic input data |
Maximum number depends on the used slave profiles |
Maximum number of total cyclic output data |
Maximum number depends on the used slave profiles |
Maximum number of cyclic input data |
Maximum number depends on the used slave profiles |
Maximum number of cyclic output data |
Maximum number depends on the used slave profiles |
Parameterization data |
|
Maximum number of acyclic read/write | Max. 220 bytes for string transfer |
Functions |
|
Baud rate | 166,67 kBaud |
AS-Interface specification | 3.0 Revision 2 |
Configuration
Configuration by tool SYCON.net (Download or exported configuration file named config.nxd).
Configuration by tool SyCon (exported configuration file named config.dbm with limitation, max. ASInterface specification 2.11).
Configuration by packets to transfer bus and slave parameters.
Diagnostic
Firmware supports common and extended diagnostic in the dual-port-memory for loadable firmware.