Key Features

  • Cyclic I/O data (Implicit Messaging): class 0 / class 1
  • Acyclic data (Explicit Messaging): Unconnected / Connected (class 3)
  • Connection Application Types: Exclusive Owner, Input Only, Listen Only
  • Trigger Types: Cyclic, Change of State, Application Triggered
  • Device Level Ring (DLR) - Media Redundancy
  • Address Conflict Detection (ACD)
  • Quality of Service (QoS)
  • CIP Sync
  • QuickConnect (Fast Startup)
  • NULL-ForwardOpen
  • CIP Safety "Ready" (provides all necessary features and interfaces to attach a CIP Safety stack on top)
  • Firmware built-in CIP Object model can be extended by additional CIP objects (e.g. to support CIP profiles)

Supported Protocols

  • TCP/IP, UDP/IP
  • DLR
  • DHCP / BOOTP
  • IEEE 802.3
  • IEEE  802.1Q
  • LLDP
  • SNMP
  • PTP (Precision Time Protocol)

Technical Data

The technical data of the individual available firmwares differ slightly. Therefore, the below table only provides a rough overview of the supported features.
For a detailed listing of the technical data, please refer to the data sheet of the individual firmware.

Note: Firmware data sheets are available for version V3.8.0.0 and higher. You can find them in the "Resources" section.


FeatureDescription
Maximum number of input data per assembly instance

504 bytes

Maximum number of output data per assembly instance504 bytes
Maximum number of assemblies
(firmware dependent)
10
IO Connection Types (implicit)

Exclusive Owner, Listen Only,

Input only
IO Connection Trigger Types

Cyclic, minimum 1 ms*
Application Triggered, minimum 1 ms*
Change Of State, minimum 1 ms*

Explicit MessagesConnected (class 3) and unconnected
Unconnected Message Manager (UCMM)supported
Max. number of connections
(firmware dependent)

Class 1: 5

Class 3: 10

UCMM: 10

Max. number of user specific objects
(firmware dependent)
20
Predefined standard objects

Identity Object (0x01)
Message Router Object (0x02)
Assembly Object (0x04)
Connection Manager (0x06)
DLR Object (0x47)
QoS Object (0x48)
TCP/IP Interface Object (0xF5)
Ethernet Link Object (0xF6)
LLDP Management Object (0x109)
Time Sync (0x43)

DHCPsupported
BOOTPsupported
Baud rates10 and 100 MBit/s
Duplex modesHalf Duplex, Full Duplex, Auto-Negotiation
MDI modesMDI, MDI-X, Auto-MDIX
Data transport layerEthernet II, IEEE 802.3
Address Conflict Detection (ACD)supported
DLR (ring topology)supported
Integrated switchsupported
CIP Reset servicesIdentity Object Reset Service of Type 0 and 1