Title 1
...
Introduction
This Application note explanes, how to configure a generic modular adapter, when the entry for "ProxyConnect" is not described in the Ethernet/IP Slave Device Description (EDS).
Please refer to the following FAQ: "Why does my modular EDS file not work?" → https://kb.hilscher.com/pages/viewpage.action?pageId=18616112
As an example the Allen Bradley Point I/O Module Adapter "1734 AENT" is used, together with the fitting Point I/O Modules "1734 IB8" and "1734 OB8E".
Configuration Example
Hardware configuration
Slot | Module Name | EDS File |
---|---|---|
0 | 1734 AENT | 0001000C006C0300.eds |
1 | 1734-IB8 | 0001000700D80300.eds |
2 | 1734-OB8E | 0001000700DA0300.eds |
The EDS File of each module is needed for further configuration of the Generic Modular Adapter.
These can be found on the Rockwell Automation Page: https://www.rockwellautomation.com/de_DE/detail.page?pagetitle=Electronic-Data-Sheets&content_type=overview&docid=11432fc64a2a887b85011582be53806b