Now the Connection Path has to be filled in. The Connection Path is described in the EDS here:
Switch back to EZ-EDS, select “Connection1” in the left tree view.
Click the Button "Decode Path". A new Window will pop up. Select decimal format in this dialog and now the instance ID can be read out for Configuration in Sycon.net.
Based on above information, the assembly Instance ID can be specified.
The instance "20 04 24 67 2C BE 2C 04" can also be decoded manually as follows:
20 04 | 24 67 | 2C BE | 2C 04 |
---|---|---|---|
Logical Segment, Class ID 0x04(4) | Configuration path, instance ID 0x67(103) | O2T Connection Point, output Assembly instance ID 0xBE(190) | T2O Connection Point, input Assembly instance ID 0x04(4). |