Now the Connection Path has to be filled in. The Connection Path is described in the EDS here:

Image Added

Switch back to EZ-EDS, select “Connection1”  in the left tree view.

Click the Button "Decode Path". A new Window will pop up. Select decimal format in this dialog and now the instance ID can be read out for Configuration in Sycon.net.

Image Added

Based on above information, the assembly Instance ID can be specified.

Image Added


The instance "20 04 24 67 2C BE 2C 04" can also be decoded manually as follows:

20 0424 672C BE2C 04

Logical  Segment, 

Class ID 0x04(4)

Configuration path, 

instance ID 0x67(103)

O2T Connection Point, 

output Assembly instance ID 0xBE(190)

T2O Connection Point,

input Assembly instance ID 0x04(4).

Configure Input assembly length

Configure 1734-OB8E