Please refer to the following FAQ: "Why does my modular EDS file not work?" → https://kbhilscher.hilscheratlassian.comnet/wiki/pages/viewpage.action?pageId=18616112113541135

As an example the Allen Bradley Point I/O Module Adapter "1734 AENT" is used, together with the fitting Point I/O Modules "1734 IB8" and "1734 OB8E".

...

The instance "20 04 24 66 2C 64 2C 65" can also be decoded manually as follows:

20 0424 67662C 642C 65

Logical  Segment, 

Class ID 0x04(4)

Configuration path,

instance ID 0x66 (102)

O2T Connection Point,

output Assembly instance ID 0xBE 0x64 (100)

T2O Connection Point,

input Assembly instance ID 0x04 0x65 (101).

Configure Input assembly length

...