Due to a major stack update of the firmware, the DTMs for the netTAP 100 are changed in SYCON.net. During the configuration of a netTAP 100 devices it is possible to choose between different DTMs in order to define the desired protocol combination:
To enable the configuration of netTAP 100 gateways with the old and new firmware, use the following DTMs for the respective firmware version: DTM name | Firmware version |
---|
Open Modbus/TCP V3 | V2.0.0.0x | POWERLINK Controlled Node V3 | V2.0.0.0x | PROFINET IO Controller V3 | Do not use. Please use PROFINET IO Controller instead. | Open Modbus/TCP | V1.7.0.8x | POWERLINK Controlled Node | V1.7.0.8x | PROFINET IO Controller | V1.7.0.8x | Others | V2.0.0.0 x and V1.7.0.8x |
The version of the firmware is shown when the desired conversion is selected. (See here (1)). The EDS files related to the firmware version are provided in different folders: ..\ Firmware,_EDS,_Examples,_Webpages\Firmware_&_EDS\netTAP 100\DeviceDescription\V1.7.0.8 x and V2.0.0.0 x respectively |