Technical Data
Feature | Description |
---|---|
Maximum number of cyclic RY data Maximum number of cyclic RX data Maximum number of cyclic RWw data Maximum number of cyclic RWr data | 128 bytes (1024 bits) 128 bytes (1024 bits) 512 words (16 bit) 512 words (16 bit) |
Occupied stations | 1 … 16 (1 station has 64 bits RY data, 32 words RWw data, 64 bits RX data, and 32 words RWr data) |
Acyclic communication | SLMP Server and Client |
UDP ports | Cyclic data 61450 (UDP) Discovery and SLMP Server 61451 (UDP) SLMP Parameter 45237 (UDP) SLMP Communication 20000 (UDP) |
Data transport layer | Ethernet II, IEEE 802.3, 100 MBit/s |
Configuration
Configuration is done by sending packets to the stack or by using SYCON.net configuration database.
Diagnostic
Some elementary diagnosis information can be read using the service “Get Status Service”.
...