Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Q

Which instances does my Ethernet IP Adapter use?

A

During the configuration of an Ethernet/IP Scanner, commonly the EDS file provided together with the Ethernet/IP Adapter can be imported.

In some cases, the connection parameters need to be defined manually.


One of the most important parameters here, are the connection instances for Input (O → T), Output (T → O) and Configuration (CFG).


These instance can be extracted from the provided EDS file.

To find out all needed parameters, the Tool EZ-EDS can be used.

https://www.odva.org/subscriptions-services/software/ez-eds-download/

Therefore


For this:

- open the EDS File, using the tool

- open the required connection type. Now you can see all required connection parameters:

Image Added


- by clicking "Decode Path", you can also see the Path information (Class / Instance / Attribute).

Image Added


In this example, there is no configuration path used. Therefore, EZ-EDS shows "Ignored Path", where the Configuration Path is commonly placed.

See also...