Key Features
- PROFIBUS DP-V0
- PROFIBUS DP-V1 class 1 and 2
- Automatic baud rate detection
Supported State Machines
- FSPMS (Fieldbus Service Protocol Slave state machine)
- MSCY1S (Master to Slave cyclic state machine)
- DMPMS (Data Link Mapping Protocol Slave state machine)
- MSAC1S (Master Class1 to Slave acycliec state machein)
- MSAC2S (Master Class2 to Slave acyclic state machine)
- MSRM2S (Master Class2 to Slave resource Manager state machine)
On this page
Technical Data
Feature | Description |
---|---|
Maximum number of cyclic input data | 244 bytes |
Maximum number of cyclic output data | 244 bytes |
Maximum number of acyclic read/write | 240 bytes |
Configuration data | Max. 244 bytes |
Parameter data | 237 bytes application specific parameters |
Acyclic communication | DP V1 Class 1 Read/Write DP V1 Class 1 Alarm DP V1 Class 2 Read/Write/Data Transport |
Baud rate | Fixed values ranging from 9,6 kBits/s to 12 MBit/s Auto-detection mode is supported |
Data transport layer | PROFIBUS FDL |
Configuration
Configuration by packets to transfer config parameters or by using SYCON.net configuration database.
Diagnostic
Firmware supports common and extended diagnostic in the dual-port-memory for loadable firmware.