Features
Key Features
- PROFIBUS DP-V0
- PROFIBUS DP-V1 class1 and 2
Supported State Machines
- FSPMM (Fielbus Service Protocol Master state machine)
- MSCY1M (Master to Slave cyclic state machine)
- DMPMM (Data Link Mapping Protocol Master state machine)
- MSAL1M (Master Class1 to Slave Alarm state machine)
- MSAC1M/MSAC2M (Master Class1/2 to Slave Acyclic state machine)
- MMAC2 (Master to Master Acyclic state machine)
- MSCS1M (Master to Slave Clock Sync state machine)
On this page
Â
Technical Data
Feature | Description |
---|---|
Maximum number of supported DPV0/DPV1 slaves | 125 |
Maximum number of total cyclic input data | 5712 bytes |
Maximum number of total cyclic output data | 5760 bytes |
Maximum number of cyclic input data | 244 bytes/slave |
Maximum number of cyclic output data | 244 bytes/slave |
Maximum number of configuration data | 244 bytes/slave |
Maximum number of parameterization data | 7 bytes/slave standard parameter 237 bytes/slave user specific parameter |
Acyclic communication | DP-V1 Class1 Read/Write DP-V1 Class1 Alarm DP-V1 Class2 Initiate/Read/Write/Data transport/Abort |
Maximum number of acyclic read/write/data transport | 240 bytes/slave |
Features | Configuration in Run |
Redundancy function | supported (requires host application programm support) |
Baudrate | Fixed values from 9.6 kbits/s to 12 Mbits/s Auto-detection mode is not supported. |
Data transport layer | PROFIBUS FDL |
Configuration
Configuration by packets to transfer bus parameters and slave data sets or by using SYCON.net configuration database.