What are the know issues of Profinet V2.33 Certification Bundle of April, 2016?

Q

What are the know issues of Profinet V2.33 Certification Bundle of April, 2016?

A

For the Profinet Certification Tools with versions:

  • RT Tester V2.33.0.4442
  • Automated RT Tester (ART) V2.33.0.7
  • Spirta V2.33.0.1003
  • TED Check V2.33.0.0002
  • Security Level 1 Test V1.4.1

The following issues are known:

RT Tester

  • Testcases DIFF_ACCESSWAYS and DIAGNOSIS will fail if the device reports a diagnosis for any Non-PDev Submodule. This can happen when for example submodules report an application diagnosis due to an operating condition. (E.g. Missing/wrong parameters, Operating Voltages...)
  • The testcase CHECK_MAUTYPE always fails when fiber optic Ethernet is used. This is an error in testcase.

Automated RT Tester

  • The tester expects a wrong error code when checking DHCP Parameters option: As the DHCP option is not supported at all by Hilscher PNS V3 and PNS V4 the correct error code is "Unsupported Option" (0x01) but the tester expects "Unsupported Suboption" (0x02)
  • The tester reports an error if the device's DCP Identify Response contains a OEMDeviceIDBlock.  According to Profinet Specification it is allowed to return such a block.
  • The Tester requires a positive response for invalid DCP Set-IP with following parameters  IP:192.168.0.50, Subnetmask: 255.255.255.0, Gateway: 0.255.255.255

TED Check

  • The IP address of the ANEL power outlet must be set to 192.168.0.244 and the host IP address must be set to 192.168.0.243. Other IP address settings are not supported.
  • All devices attached to the ANEL power outlet must be powered on and fully started before the check is executed. The web interface of the Power Outlet can be used for this purpose.

SPIRTA

  • all tests fail when fiber optic Ethernet is used. This is an error in SPIRTA.