Ethernet/IP - Configuration of Generic Modular Adapter [EN]

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Next »


Introduction

This Application note explanes, how to configure a generic modular adapter, when the entry for "ProxyConnect" is not described in the Ethernet/IP Slave Device Description (EDS).

Please refer to the following FAQ: "Why does my modular EDS file not work?" → https://kb.hilscher.com/pages/viewpage.action?pageId=18616112

As an example the Allen Bradley Point I/O Module Adapter "1734 AENT" is used, together with the fitting Point I/O Modules "1734 IB8" and "1734 OB8E".

Hardware configuration

SlotModule NameEDS File
01734-AENT0001000C006C0300.eds
11734-IB8        0001000700D80300.eds
21734-OB8E    0001000700DA0300.eds

The EDS File of each module is needed for further configuration of the Generic Modular Adapter.

These can be found on the Rockwell Automation Page:

https://www.rockwellautomation.com/de_DE/detail.page?pagetitle=Electronic-Data-Sheets&content_type=overview&docid=11432fc64a2a887b85011582be53806b

Software Configuration

Add Modules

In SYCON.net, add an EtherNet/IP Scanner (e.g. CIFX RE/EIM) and then add an ENIP Modular Generic Adapter to the network.

Open the Configuration Window of the Modular Generic Adapter an choose "Modules" in the Navigation Area.

Change “Slots in Rack” to 3 and add the modules:

Configure 1734-AENT


Configure 1734-IB8


Configure 1734-OB8E