Ethernet/IP - Configuration of Generic Modular Adapter [EN]

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 12 Next »


Introduction

This Application note explanes, how to configure a generic modular adapter, when the entry for "ProxyConnect" is not described in the Ethernet/IP Slave Device Description (EDS).

Please refer to the following FAQ: "Why does my modular EDS file not work?" → https://kb.hilscher.com/pages/viewpage.action?pageId=18616112

As an example the Allen Bradley Point I/O Module Adapter "1734 AENT" is used, together with the fitting Point I/O Modules "1734 IB8" and "1734 OB8E".

Hardware configuration

SlotModule NameEDS File
01734-AENT0001000C006C0300.eds
11734-IB8        0001000700D80300.eds
21734-OB8E    0001000700DA0300.eds

The EDS File of each module is needed for further configuration of the Generic Modular Adapter.

These can be found on the Rockwell Automation Page:

https://www.rockwellautomation.com/de_DE/detail.page?pagetitle=Electronic-Data-Sheets&content_type=overview&docid=11432fc64a2a887b85011582be53806b

Software Configuration

Add Modules

In SYCON.net, add an EtherNet/IP Scanner (e.g. CIFX RE/EIM) and then add an ENIP Modular Generic Adapter to the network.

Open the Configuration Window of the Modular Generic Adapter and choose "Modules" in the Navigation Area.

Change “Slots in Rack” to 3 and add the modules:

Configure 1734-AENT


Configure 1734-IB8

Specify Connection

EtherNet/IP is a connection-oriented protocol, therefore the connection should always be specified first.

Open the EDS for 1734-IB8 and go to the section [Connection Manager], assuming that Connection23 (Input  only) will be used:

Configure connection settings

Please choose "Connection" in the Navigation Area of the Modular Generic Adapter. Select  the Module “Slot<1> 1734-IB8”.

Decode the field "trigger & transport" and "realtime format", which are defined in Connection23.

These parameters describe the connection variables, which have to be filled in the Connection configuration Window in Sycon.net.


The free Tool "EZ-EDS" from ODVA (https://www.odva.org/software/EZ-EDS-Download), can be used to make decoding of the parameters easier.

Therefore, open the EDS by selecting "File → Open…”.  Select "Generic EDS" as EDS type and ignore the upcoming error messages.

When the file is successfully opened, select “Connection1” in the left tree view.

The name “Connection23” in EDS file is automatically converted to “Connection1”.

The following dialog window:

Based on these informations, now configure the Connection Area in Sycon.net:

Don't forget, to set the Connection name to "Connection23".

Configure assembly instance ID

Choose "Assembly" in the Navigation Area of the Modular Generic Adapter now. Select  the Module “Slot<1> 1734-IB8”.

Now the Connection Path has to be filled in. The Connection Path is described in the EDS here:

Switch back to EZ-EDS, select “Connection1”  in the left tree view.

Click the Button "Decode Path". A new Window will pop up. Select decimal format in this dialog now the instance ID can be read out for Configuration in Sycon.net.

Based on above information, the assembly Instance ID can be specified.


The instance "20 04 24 67 2C BE 2C 04" can also be decoded manually as follows:

20 0424 672C BE2C 04

Logical  Segment, 

Class ID 0x04(4)

Configuration path, instance ID 0x67(103)

O2T Connection Point, output Assembly instance ID 0xBE(190)

T2O Connection Point, input Assembly instance ID 0x04(4).

Configure Input assembly length

Configure 1734-OB8E