Technical Data
Feature | Description |
---|---|
Maximum number of input data | 504 bytes per assembly instance |
Maximum number of output data | 504 bytes per assembly instance |
IO Connection Types (implicit) | Exclusive Owner, Listen Only, Input only |
IO Connection Trigger Types | Cyclic, minimum 1 ms* |
Explicit Messages | Connected and unconnected |
Max. number of connections | 8 (sum of connected explicit and implicit connections) |
Max. number of user specific objects | 20 |
Unconnected Message Manager (UCMM) | supported |
Predefined standard objects | Identity Object (0x01) |
DHCP | supported |
BOOTP | supported |
Baud rates | 10 and 100 MBit/s |
Duplex modes | Half Duplex, Full Duplex, Auto-Negotiation |
MDI modes | MDI, MDI-X, Auto-MDIX |
Data transport layer | Ethernet II, IEEE 802.3 |
Address Conflict Detection (ACD) | supported |
DLR (ring topology) | supported |
Quick Connect | supported |
Integrated switch | supported |
CIP Reset services | Identity Object Reset Service of Type 0 and 1 |
Configuration
Configuration is done by sending packets to the stack or by using SYCON.net configuration database.
...