Features

Key Features

  • Remote I/O Station (I/O points only)
  • Remote Device Station (I/O points and words)
  • Configurable number of occupied stations (1-4)

  • Configurable number of extension cycles (1, 2, 4 or 8)
  • Configurable vendor code and model type

Supported Protocols

  • Support of both (configurable):
    • CC-Link Version 2.0 and
    • CC-Link Version 1.11
On this page

 

Technical Data

The data below applies to the CC-Link firmware and stack version V2.7.x. The firmware/stack supports CC-Link Version 2.0 and 1.11

This firmware/stack has been written to meet the requirements outlined in the CC-Link specification Ver.2.00 BAP-05026-J.

FeatureDescription
Data for firmware/stack working according to CC-Link Version 2.0

Station Types

Remote device station, up to four occupied stations
Maximum input data368 bytes
Maximum output data368 bytes
Input data remote device station112 bytes (RY) and 256 bytes (RWw)
Output data remote device station112 bytes (RX) and 256 bytes (RWr)
Extension cycles1, 2, 4, 8
Baud rates156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
Data for firmware/stack working according to CC-Link Version 1.11
Station TypesRemote I/O station, remote device station, up to 4 occupied stations
Maximum input data48 bytes
Maximum output data48 bytes
Input data remote I/O station4 bytes (RY)
Output data remote I/O station4 bytes (RX)
Input data remote device station4 bytes (RY) and 8 bytes (RWw) per occupied station
Output data remote device station4 bytes (RX) and 8 bytes (RWr) per occupied station
Baud rates156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s

Configuration

Configuration by packet to transfer warm start parameters

Diagnostic

Firmware supports common and extended diagnostic in the dual-port-memory for loadable firmware