CC-Link is an open industrial network that enables devices from numerous manufacturers to communicate. It is predominantly used in machine, cell or process control applications in manufacturing and production industries, but can also be used in facilities management, process control and building automation. [Wikipedia, 2013-10-18]
- CC-Link uses a RS-485 compliant interface
- Shielded twisted pair
- Up to 64 stations per network
Hardware
Hardware interface with recommended parts
- CLPA provides list of recommended parts
- Filter, RS-485 Driver, Zener diode, Optocoupler
- Recommended part list allows 5 V technology only
Communication errors likely when using none recommended RS-485 Driver!
On this page
Block diagram
Certification
- Conformance test centers in Japan and Ratingen/Germany by Mitsubishi
- Manufacturer pre-test and test at laboratory
- Hardware and software tests
- Conformance test when recommended parts are used only
- Test with 2 devices
- Conformance test when none recommended parts are used
- Test with 2 devices
- AND additional tests with up to 42 devices
Cable Length
Maximum overall cable extension length
Communication Speed | Maximum Length |
---|---|
156 kbps | 1200 m |
625 kbps | 900 m |
2,5 Mbps | 400 m |
5 Mbps | 160 m |
10 Mbps | 100 m |
Applicable Specification(s)
- CC-Link Specification Ver.2.00, BAP-05026-J