CC-Link is an open industrial network that enables devices from numerous manufacturers to communicate. It is predominantly used in machine, cell or process control applications in manufacturing and production industries, but can also be used in facilities management, process control and building automation. [Wikipedia, 2013-10-18]

  • CC-Link uses a RS-485 compliant interface
  • Shielded twisted pair
  • Up to 64 stations per network
Hardware

Hardware interface with recommended parts

  • CLPA provides list of recommended parts
    • Filter, RS-485 Driver, Zener diode, Optocoupler
    • Recommended part list allows 5 V technology only

(warning)  Communication errors likely when using none recommended RS-485 Driver!

On this page

Block diagram

Certification

  • Conformance test centers in Japan and Ratingen/Germany by Mitsubishi
  • Manufacturer pre-test and test at laboratory
    • Hardware and software tests
  • Conformance test when recommended parts are used only
    • Test with 2 devices
  • Conformance test when none recommended parts are used
    • Test with 2 devices
    • AND additional tests with up to 42 devices

Cable Length

Maximum overall cable extension length

Communication SpeedMaximum Length
156 kbps1200 m
625 kbps900 m
2,5 Mbps400 m
5 Mbps160 m
10 Mbps   100 m

Applicable Specification(s)

  1. CC-Link Specification Ver.2.00, BAP-05026-J